Commercial Split Ducted Indoor Unit – Reverse Cycle
Provides installation versatility and maximum efficiency in cooling performance, air handling and filtering in cooling or heat pump applications.
Models have a dual distribution system for two stage capacity control during cooling cycles.
Units are convertible to up-flow or horizontal design.
Key Features
-
Multi-Circuit, Copper Tube Coil
Extra large surface area of Lennox designed coil provides maximum cooling efficiency, excellent heat transfer and low air resistance. Coils on 090-240 models are face split with separate circuits, each circuit has its own expansion valve. -
Expansion Valve
For use with R-410A systems.
Factory installed and piped.
Multi-circuit coils are equipped with one thermal expansion valve per circuit.
Valves are sized for best performance.
090 and 120 models have internal check valves for use with heat pump systems. -
Refrigerant Piping and Drain Connections
Refrigerant line inlets (knockouts) are provided on both sides of the cabinet.
Refrigerant lines require sweat connections and are made internal to the cabinet. -
Filters
51 mm thick, throwaway fiberglass media filters are furnished as standard. Filter rack design permits quick and easy removal of filters for servicing. -
Belt Drive Blowers
090-120-150 models are equipped with a single blower wheel. 180 and 240 models have dual blower wheels. Centrifugal belt driven blowers deliver large air volumes quietly and with low power consumption. -
Control Box
Control box is located in separate compartment in unit cabinet. The box may be relocated to an alternate location for easier access depending on application. -
Cabinet
Cabinet is constructed of heavy-gauge, galvanized steel. Cabinet is completely lined with thick fiberglass insulation resulting in quiet and efficient operation due to the excellent sound deadening and insulating qualities of fiberglass. -
Drain Pan
Deep, corrosion resistant plastic drain pan. Reversible drain pan allows for drain outlets on either end of cabinet and can be repositioned for horizontal air flow applications. Drain pan is removable from either side in both horizontal and vertical applications.
Specifications
Model |
Indoor / Outdoor |
TAA180S4D / TPA090S4D (x2) |
|
Performance |
Cooling |
Heating |
|
Rated Capacity |
kW |
43.60 |
40.60 |
Sensible Capacity |
kW |
38.26 |
|
Input Power |
kW |
12.94 |
10.98 |
AEER / ACOP |
W/W |
3.232 |
3.525 |
Rated Air Flow |
Indoor (L/S) |
2830 |
|
Outdoor (L/S) |
3270 (x2) |
||
Electrical |
|||
Volts / Hz / Phase |
Indoor |
415 / 50 /3 |
|
Outdoor |
415 / 50 /3 |
||
Full Load Amps |
Outdoor (A) |
14.8 (x2) |
|
Interconnecting Wire |
mm2 |
0.75 x 6 Core (24V) |
|
Installation |
|||
Unit Dimensions W x H x D |
Indoor (mm) |
2445 x 749 x 1390 |
|
Outdoor (mm) |
1470 x 1238 x 1050 (x2) |
||
Weight Nett/Gross |
Indoor (kg) |
680 / 760 |
|
Outdoor (kg) |
197 / 209 (x2) |
||
Spigot Connection Size |
Supply (mm) |
1311 x 473 |
|
W x H |
Return (mm) |
1505 x 524 |
|
Refrigerant (Field Supplied) |
R410A (kg) |
7.7 (x2) |
|
Factory Holding Charged |
R410A (kg) |
0.45 (x2) |
|
Max Pipe Run |
M |
60 |
|
Pipe Sizes Up to 15M |
mm (inch") |
15.9 x 34.9 (5/8" & 1-3/8" x 2) |
|
Drain Pipe Connection |
mm |
25mm |
Accessories
Electric Heat Section (Optional)
Furnished in a separate add-on matching cabinet.
Mounting hardware is furnished to secure cabinets together.
Pre-punched mounting holes are furnished for aligning electric heat section to air handler supply air flange.
Removable panel permits service access.
Electrical inlet provides wiring entry.
Hot Water Coil (Optional)
Furnished in a separate add-on matching cabinet.
Mounting hardware is furnished to secure cabinets together.
Pre-punched mounting holes are furnished for aligning cabinet to air handler.
Cabinet is reversible to allow piping on either side of unit.
Lennox designed and built coil has large face area, excellent heat transfer and low air resistance.
Constructed of precisely spaced ripple-edged aluminium fins fitted to durable copper tubes.
Economizer Damper Section (Optional)
Factory assembled and wired economizer dampers and controls are available for field installation.