Reverse Cycle Rooftop Unit
A total package of quality and technology.
A Lennox Landmark Packaged Unit offers legendary Lennox quality, along with outstanding performance and reliability for commercial buildings. From the innovative engineering to the durable cabinet, these units are built to deliver exceptional comfort — season after season, year after year.
Available in Heat Pump (KHA) or Cooling Only (KCA) models
Key Features
-
High Efficiency
Unit is designed to meet or exceed ASHRAE 90.1-2004 standards. -
Comfort/ IAQ
Corrosion-resistant, removable, double-sloped drain pan provides application flexibility, durability and improved serviceability.
With Cooling Only units, it is possible to field install an electric heating unit on an existing unit and convert it to a heat pump at a later date. Helix wound nichrome elements are used for this purpose.
An individual element limit control provides better control over your air conditioning needs. -
Serviceability
Hinged access panels provide quick access to components and protect panels and roof from damage during servicing.
Full-perimeter base rail provides greater structural integrity, so the unit is easier to handle when rigging and transporting.
Isolated compressor compartment allows performance check during normal compressor operation without disrupting airflow.
Fork slots on three sides make it easy to pick up and transport units from almost any angle.
Independent motor mount allows for easy and efficient service access without removing the top panel. -
Reliability
Pre-defined supply fan motor/drive combinations make selecting components to meet static and airflow requirements quick and easy.
Thermostatic expansion valves provide peak cooling performance across the entire application range.
Scroll compressor provides reliable, long-term operation.
Specifications
Model Number |
KHA072S4B |
|
Performance |
||
Rated Cooling Capacity |
kW |
17.0 |
Sensible Cooling Capacity |
kW |
15.0 |
Rated Heating Capacity |
kW |
15.8 |
Efficiency Rating AEER |
3.496 |
|
Efficiency Rating ACOP |
|
3.685 |
Nominal Airflow |
L/s |
1040 |
Sound Power |
dB(A) |
83 |
Compressor Type |
Qty |
Scroll (1) |
Electrical |
||
Power Supply Voltage |
V |
415 |
Full Load Current (Base Model) |
A |
14.7 |
Installation |
||
Unit Dimensions |
mm |
2165 x 1192 x 1191 |
Weight (Base model) |
kg |
340 |
Refrigerant Type |
|
R410A |
Accessories
Field-installed accessories
Field-powered GFI
Disconnects
Economizers with single or dual enthalpy control
Electric heat
50% constant volume powered exhaust fan
CO2 sensor
Return and supply air smoke detectors
Low ambient kits
Hail guards
Coil guards
Link to the L Connection® Network line of commercial controls with an optional Network Thermostat Controller
LPG Conversion Kit (gas/electric only)
-40°F cold weather kit (gas/electric only)
Combustion air intake or flue exhaust extensions (gas/electric only)
Blower proving switch
Dirty filter switch
Manual outdoor air dampers (25%)
Motorized outdoor air dampers
Factory-installed options
Coil corrosion protection
Stainless steel heat exchanger
Hinged doors
Factory options or field accessories
Economizers
Barometric relief dampers
High- and low-static drive kits